WS-15 - R22; R407C

Technical Data

Cooling capacity (1)

Watt

4440

Btu/h

15150

Heating capacity (1)

Watt

6532

Btu/h

22286

Power Consumption (2)

Cooling

Watt

1139

Heating

Watt

1256

Operating Current (2)

Cooling

Amp.

6.5

Heating

Amp.

6.4

C.O.P

Cooling

 

3.9

Heating

 

4.2

Air Flow

M3/h

850

CFM

500

Net Static Pressure (3)

mm H2O

5

Water Flow

M3/h

1.2

GPM

5.3

Heat Rejection-Cooling

Watt

5579

Btu/h

19037

Heat Extraction-Heating

Watt

5276

Btu/h

18000

Power Supply

V/Ph/Hz

230/1/50 (4)

Time Delay Fuse

Amp.

C10

Water Piping in/out

BSP

3/4"

Drain

mm

19

Refrigerant Charge

gr.

1300

Dimensions (LxWxH)

mm

880x600x400

Net Weight

Kg.

65

 

Notes:

1.   Design data for cooling:

Air entering temperature  27C db/19C wb and water inlet temperature 29C

Design data for heating:

Air entering temperature 21C and water inlet temperature 20C

2.  Excluding electrical heating element.

3.   Net static pressure available at fan discharge at nominal capacity.

4.   Available also in 400/3/50.

5.   Data applicable to R407C and may vary up to 3% for R22.

    For additional information contact Unique ltd.

 

 

 

 

  

 

 

 

 

 

 

 

Cooling Performance

AIR Entering Temperature 24 C db/ 17 C wb

Entering Water Temp.

Water Flow

Water Pressure Drop

Cooling Capacity

Power Cons.

Heat Rejection

COP

C

F

m/hr

gpm

m. H2O

Watt

Btu/h

Watt

Watt

Btu/h

 

29

85

1

4.4

4.1

4103

14000

1077

5180

17674

3.8

29

85

1.2

5.3

4.3

4132

14100

1076

5209

17772

3.8

29

85

1.4

6.1

4.5

4132

14100

1076

5209

17772

3.8

32

90

1

4.4

4.1

4074

13900

1094

5168

17634

3.7

32

90

1.2

5.3

4.3

4103

14000

1120

5223

17821

3.7

32

90

1.4

6.1

4.5

4118

14050

1133

5251

17916

3.6

35

95

1

4.4

4.1

4030

13750

1127

5157

17595

3.6

35

95

1.2

5.3

4.3

4059

13850

1154

5213

17788

3.5

35

95

1.4

6.1

4.5

4074

13900

1178

5252

17919

3.5

 

AIR Entering Temperature 27 C db/ 19 C wb

Entering Water Temp.

Water Flow

Water Pressure Drop

Cooling Capacity

Power Cons.

Heat Rejection

COP

C

F

m/hr

gpm

m. H2O

Watt

Btu/h

Watt

Watt

Btu/h

 

29

85

1

4.4

4.1

4367

14900

1104

5471

18666

4.0

29

85

1.2

5.3

4.3

4440

15150

1139

5579

19037

3.9

29

85

1.4

6.1

4.5

4455

15200

1152

5606

19129

3.9

32

90

1

4.4

4.1

4308

14700

1167

5475

18681

3.7

32

90

1.2

5.3

4.3

4338

14800

1184

5522

18840

3.7

32

90

1.4

6.1

4.5

4367

14900

1192

5559

18967

3.7

35

95

1

4.4

4.1

4279

14600

1217

5496

18751

3.5

35

95

1.2

5.3

4.3

4279

14600

1227

5506

18786

3.5

35

95

1.4

6.1

4.5

4250

14500

1239

5489

18729

3.4

 

Heating Performance

AIR Entering Temperature 21 C

Entering Water Temp.

Water Flow

Water Pressure Drop

Heating Capacity

Power Cons.

Heat Extraction

COP

C

F

m/hr

gpm

m. H2O

Watt

Btu/h

Watt

Watt

Btu/h

 

12

79

1

4.4

4.1

5510

18800

1172

4338

14800

3.7

12

79

1.2

5.3

4.3

5553

18947

1157

4396

1500

3.8

16

86

1

4.4

4.1

6113

20856

1247

4865

16600

3.9

16

86

1.2

5.3

4.3

6186

21108

1263

4924

16800

3.9

20

94

1

4.4

4.1

6526

22266

1280

4246

17900

4.1

20

94

1.2

5.3

4.3

6532

22286

1256

5276

18000

4.2

24

101

1

4.4

4.1

6786

23152

1305

5481

18700

4.2

24

101

1.2

5.3

4.3

6834

23318

1266

5569

19000

4.4

 

Data applicable to R407C and may vary up to 3% for R22. For additional information contact Unique ltd.

 