AHU-L40A

 

Horizontal Unit  

Vertical Unit - Top Air Discharge

Vertical Unit - Front Air Discharge

 

 

TECHNICAL DATA – AHU-L40A

 

 

TYPE A

Air Flow (at high speed)

m3/Hr

6800

CFM

4000

Fan Type And Model

Centrifugal

2x12"x12"

High Fan Speed

R.P.M

900

Number of Speeds

 

3

Noise Level1

dbA

54

Power

 

230v/50Hz/1Ph

Current Consumed

Amps

2x4.6

Weight2

Kg

141/145

Coil Face Area

m2

0.74

Fins Spacing

Per Inch

12 for 4-row coil

10 for 6-row coil

Air Flow refers to 4 row coil and 4 mm H2O external pressure drop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 Noise level refers to a ducted unit at a distance of 1.5m from the unit.

2 Horizontal unit/Vertical unit

Cooling Capacity

Air Entering  Temperature 26.70C DB

19.40C WB

4 Row Coil

6 Row Coil

EWT 0C

WTR 0C

CAP Watt

CAP 

 Btu/h

WF m3/HR

 PD     

m H2O

CAP Watt

CAP   Btu/h

WF m3/HR

 PD     

m  H2O

7.2

5.5

37012

126359

5.7

2.3

41589

141985

7.2

1.9

 

 

 

 

 

Heating Capacity

Air Entering  Temperature 210C

1 Row Coil

2 Row Coil

EWT 0C

WTR  0C

CAP Watt

CAP   Btu/h

WF m3/HR

  PD      m  H2O

CAP Watt

CAP  Btu/h

WF m3/HR

 PD      m  H2O

90

20

41100

140315

1.8

2.5

72800

248539

3.1

3.2

 

 

 

 

 

WTR- Water Temprature Raise EWT- Entering Water Temprature CAP- Cooling Capacity

 PD- Pressure Drop WF- Water Flow

 

For additional information see attached Data Sheet

Data Sheet  Data Sheet

Product specifications are subject to change without notice.
Appearance of products may differ slightly from catalog.
PrintTell a friendSubmit response